2. The rated current of ABB miniature circuit breaker thermal release shall be slightly larger than the load current in the line. (if the protection object is a conductor, the rated current of the circuit breaker shall be slightly smaller than the safe current carrying capacity of the conductor.)
3,ABB微型断路器的极限分断电流要大于电路可能出现的最大短路电流。
3. The limit breaking current of ABB miniature circuit breaker shall be greater than the maximum short-circuit current that may occur in the circuit.
4. If the impulse current in the line of the protection object is relatively large, the instantaneous tripping value and action time of the circuit breaker shall be considered. For example, the starting current of the motor circuit is generally 4-7 times of the rated current. If it is heavy load, the starting current will be greater. When ABB miniature circuit breaker is selected as low protection, ABB miniature circuit breaker with rated current slightly greater than the rated current of the motor (1.2-1.5 times of the rated current of the motor) and instantaneous action value greater than the maximum starting current of the motor shall be selected.
5. Selection of the number of poles: the number of poles of ABB miniature circuit breaker shall be reasonably selected according to the number of phase lines and zero lines to be controlled. 1p or 2p for single-phase power supply and 3P or 4P for three-phase power supply.